Micromod RetroPAK: SLC Configuration Manual Manual do Utilizador Página 91

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 394
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 90
Command Series Migration to MOD 30ML
Pre-configured Single Loop PID Control
To configure the inputs:
Open the AIN block AIN1 for input 1. See figure below:
Figure P1.2.
PID with Local SP
You can change the Input Type and Linearization Type for the built-in input 1 here.
Specify the Input Signal Range also.
The VCI block ENG UNITS 1 in the loop compound is used for converting the voltage,
millivolts or current input signal to engineering units. See figure below:
Change the Linearization type (Linear, Square, Square root, Modified Square, Modified
Square root) as required for the input signal and specify the Engineering Range and
Quality Limits.
P1- 5
Vista de página 90
1 2 ... 86 87 88 89 90 91 92 93 94 95 96 ... 393 394

Comentários a estes Manuais

Sem comentários