Command Series Migration to MOD 30ML
Function Code 16 – Multiply
Figure 16 .2.
Function Code 16
INPUTS - OUTPUTS
Signal Block Type Description
S1 FC16 Input – S1
Floating Point
Connect to the FC16.S1 signal of
the compound. Input1 to the
multiplier function.
S2 FC16 Input – S2
Floating Point
Connect to the FC16.S2 signal of
the compound. Input2 to the
multiplier function.
S3 FC16 Input – S3
Floating Point
Connect to the FC16.S3 signal of
the compound. Scalar (gain)
(default value =1)
N FC16 Output – R
Floating Point
Connect from the FC16.N signal
of the compound. Result of the
calculation.
16 - 2