Command Series Migration to MOD 30ML
Function Codes – Gallery Tutorial
Figure 2 .39.
Cancel Connection
17. Connect the PID output from the compound to the analog output:
Select the connector and then click on the FC156 PID (PV/LOCAL SP) compound and
click on it. The Choose Parameter menu will be displayed as shown below: Select PID.N
from the menu and click on OK.
Figure 2 .40.
Choose Parameter
Drag the connection line to left of the AOUT block and connect to the Input point. The
connected blocks and the compound will look like in the next figure:
2 - 28