Command Series Migration to MOD 30ML
Function Code 36 – Qualified OR
S7 FC36 Input – S7 Boolean
(Discrete)
Connect to the FC36.S7 signal of the
compound. Input S7 to the OR function.
S8 FC36 Input – S8 Boolean
(Discrete)
Connect to the FC36.S8 signal of the
compound. Input S8 to the OR function.
S9 FC36 Input – S9 COUNT Specify a value I the block configuration.
S9 specifies the number of inputs that
must equal logic 1.
S10 FC36 Input – S3 Boolean
(Discrete)
Connect to the FC36.S10 signal of the
compound. S10 specifies the select inputs.
0 = no. of logic 1 inputs >= S9
1 = no. of logic 1 inputs = S9
36 - 4