Single Loop Process Controller Instruction Manual
Analog Backup Controller 71
6.3.1 Abbreviated Configuration Tables
Table 6-2 through Table 6-8 are provided as a quick reference source for the configuration datapoints.
These tables do not have the definition column; therefore, for the initial instrument configuration, Section 4
should be referenced until each datapoint functionality can be recognized by its title. These tables are pro-
vided because even though the functionality of the datapoints can eventually be recognized by title, the
specific datapoint locations can not always be remembered..
Table 6-2. Analog lnput (ANI) Module
Title Symbol
ANI0
Datapoint
ANI1
Datapoint
Default
Analog Input
(Display Only)
ANI H000 H001 0
Engineering
Span
SPAN C256 C257 100
Engineering
Zero
ZERO C276 C277 0
Digital Filter
Index
DFILT B269 B270 3
0-5 V lnput
NOBIAS L416 L417 0
Square Root
Signal
SQRT L440 L441 0
Calibrate Zero
CIZ B263 B264
Calibrate Span
CIS C296 C297
Tag Name
AITAG A224 A225 ANI0
ANI1
Engineering
Units
AIEU A298 A299 Percent
Table 6-3. Analog Output (ANO) Module
Title Symbol
ANO0
Datapoint
Default
Analog Output
(Display Only)
ANO C000
0
0 - 210 mA
Output
OZBASE
L472 0
Calibrate Zero
COZ
B267
Calibrate Span
COS
C300
Tag Name
AOTAG A244 ANO0