Single Loop Process Controller Instruction Manual
48 Configuration Parameters
Table 4-7. Contact Output Module (CCO)
Title Symbol
CCO0
Datapoint
Default Attribute
Purpose: This module allows the action of the CCO to be reversed (normally a closed contact =1, but
can be changed to = 0).
Contact Output
(Display Only)
CCO L024 0
If CCO = 0 and OINV = 0, then it is open.
If CCO = 0 and OINV = 1, then it is closed.
If CCO = 1 and OINV = 0, then it is closed.
If CCO = 1 and OINV = 1, then it is open.
Contact Output
Invert
OINV L288 0
As shown above, it reverses the action of the
CCO datapoint.
Tag Name
COTAG A280 CCO0
It is an assignable 10 character name for the
contact control output.