IB-23C650
SETUP
Table 8. Set-Point Setup Menu
Middle
Display
Bottom
Display
Entry Description
FIXED NO
YES
= Allows changes in Displays menu
= This local set-point can be changed at the
Initial Value entry only, Step 5.5.
HI LIMIT xxxx Low limit to 30000
LO LIMIT xxxx –3000 to high limit
INIT VAL xxxx Low limit to high limit
The current value of this local setpoint.
SETP SRC LAST
LOC SETP
SETPT 2
SETPT 3
SETPT 4
REM SETP
= Power up with same set-point value as at
power down
= If the chosen local set-point is ‘fixed’,
powers up with that value. Otherwise powers
up with ’fixed’ value below, Step 6.2. The
chosen local set-point does not have to be
enabled to provide the power up value.
= Power up using remote set-point, if it exists.
Otherwise, same as LAST.
91