Micromod MOD: Modcell 2050R Users Guide Manual do Utilizador Página 125

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
Vista de página 124
IB-23C650
SETUP
Table 12. Tune Menu
Middle
Display
Bottom
Display
Entry Description
RATIO xxx.xx
-300.00 to 300.00
Ratio value applied to remote set-point. If ratio
function is not required, set value to 1.
BIAS xxxx –3000 to 30000 (decimal point per Inputs)
Bias value added to or subtracted from remote
set-point. If bias function is not required, set
value to 0.
RATIO xx.xx 0.01 to 300.00
Initial value of local ratio applied to process
input. During operation, this local value can be
changed from the operator's display. If ratio
source is remote, this display provides the ratio
value.
BIAS xxxxx –30000 to 30000 (decimal point per Inputs)
Initial value of local bias applied to process
input. During operation, this local value can be
changed from the operator's display. If bias
source is remote, this display provides the bias
value.
119