MOD 30ML Operation
SETUP
2-12
Table 7. System Template Configuration (Cont’d)
Step Step Description Line 1 Line 2 Line 6 Entry Description
7C System Passwords (Entry)
∇ moves down to Step 7C1
NXT, PRV change step
SYSTEM PASWORDS
The passwords set here will restrict
access to tuning and configuration
features.
7C1 Tune Passwords
∇ ∆ changes number, ENT enters
NXT, PRV change step
TUNE PASSWORD 0
Enter a number required to access
tuning parameters.
7C2 Configure Passwords
∇ ∆ changes number, ENT enters
NXT, PRV change step
CONFIG PASSWORD 0
Enter a number required to access
configuration parameters.
7C3 Access Timeout
∇ ∆ changes number, ENT enters
NXT, PRV change step
ACCESS TIMEOUT 0
0-54 minutes; 0=infinite
The time in minutes that the tune
and configure access levels will
timeout and return to the operate
level after last keyboard activity.
7C4 System (Passwords Exit)
∆ moves up to Step 7C
NXT, PRV change step
SYSTEM
7D System Alarms (Entry)
∇ moves down to Step 7D1
NXT, PRV change step
SYSTEM ALARMS
Alarm indication rates apply to
light, display and beeper. Alarms
are: unacknowledged diagnostics,
high or low process and deviation
conditions, and input quality.
7D1 Diagnostic Flash/Beep Rate
∇ ∆ change value, ENT enters
NXT, PRV change step
DIAGNSTC RATE FAST
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D2 Diagnostic Flash
∇ ∆ change value, ENT enters
NXT, PRV change step
DIAGNSTC FLASH OFF
OFF = flashing is disabled
ENABLE = flash display (LED
always flashes for diagnostic)
7D3 Diagnostic Beep
∇ ∆ change value
DIAGNSTC BEEP ENABLE
OFF = beeping is disabled
ENABLE = beep for diagnostic
7D4 Minimum Low Alarm Priority
∇ ∆ change value, ENT enters
NXT, PRV change step
MINIMUM LOW PRI 100
All process alarms with priority >=
this value (2 - 255) are considered
LOW priority for display purposes.
7D5 High Priority Process Alarm Flash/
Beep Rate
∇ ∆ change value, ENT enters
NXT, PRV change step
HIGH PRI RATE FAST
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D6 High Priority Process Alarm Flash
∇ ∆ change value, ENT enters
NXT, PRV change step
HIGH PRI FLASH OFF
OFF = flashing is disabled
ENABLE = flash display on alarm
7D7 High Priority Process Alarm Beep
∇ ∆ change value, ENT enters
NXT, PRV change step
HIGH PRI BEEP OFF
OFF = beeping is disabled
ENABLE = beep on alarm
7D8 Low Priority Process Alarm Flash/
Beep Rate
∇ ∆ change value, ENT enters
NXT, PRV change step
LOW PRI RATE SLOW
FAST = off 100msec, on 300 msec
SLOW = off 250msec, on 750msec
7D9 Low Priority Process Alarm Flash
∇ ∆ change value, ENT enters
NXT, PRV change step
LOW PRI FLASH OFF
OFF = flashing is disabled
ENABLE = flash display on alarm
Comentários a estes Manuais