Training Manual
Single Loop Template Lab
3 - 23
3.3.12 OUTPUT Setup
1 Press DOWN to enter output section
2 Leave the default value of BI1 AOUT in
place
NONE, BI1 AOUT, BI2 AOUT, and
S01 to S11. Only available outputs are listed.
3 Press NXT
OUTPUT LO SIGNL displayed. 0% of the
output range.
4 Press NXT
OUTPUT HI SIGNL displayed. 100% of the
output range
Figure 3 .23.
5 Press NXT until OUTPUT LO LIMIT
displayed
PID output limited to this number or above.
6 Set limit to 0.0. Then press ENT
7 Press NXT, OUTPUT HI LIMIT
displayed
PID output limited to this number or below.