ICN OPC Server
Application Tutorial
Figure 3 .2.
Add new ICN
Device
Type the name MOD30ML in the Name field (the name is user-configurable and
can be anything!).
Select the Type as MOD30ML Controller from the drop down menu.
Select the serial communication port of the computer to which the MOD 30ML is
connected, in the Port field. Click on the down arrow in this field to show the drop-
down menu and then select the port. (COM1 for example).
Type the ICN Number in the ICN Number field.
Type the instrument’s address in the Instrument Address field. This is the
instrument’s ICN address on the ICN specified in the ICN Number field above.
Leave the Timeout in the default value of 1000 ms.
Timeout value in ms is the time for which the OPC server tries to re-establish
communication with the device in the case of a communication failure.
Click on OK on this dialog box. The Modcell Interface File dialog will appear
next as shown in the figure below:
3 - 3