MOD 30ML Functions
CONFIGURATION EXAMPLES
Figure 3. 26.
PAD block Properties
Change the Trip value to 150 and then click on OK to accept the changes.
The alarm label for this alarm is PROCESS HIGH. Optionally you can change the Alarm
Label for this alarm from the Display tab of the PAD block.
Click on OK to accept the changes.
Open the PAD block Lo Process Alarm by double-clicking on it. Refer to the next figure.
Change the Trip value to 50.
The alarm label for this alarm is PROCESS LOW. Optionally you can change the Alarm
Label for this alarm from the Display tab of the PAD block.