3.4.4 CONTACT OUTPUT MODULES
The contact output modules convert a logic level to a hardware contact condition. Output DO2 -
DO17 are only active if the appropriate hardware options are installed. The parameters for each
module are given below.
CONTACT OUTPUT:
The value of this datapoint along with the value of OINV determines the condition of the output
contact.
CONTACT OUTPUT INVERT:
When this datapoints value is "1", the hardware contact will be closed when the output value is
"1" and be open when the output value is "0". When the datapoints value is "0", the hardware con-
tact will be open when the output value is "1" and be closed when the output value is "0".
TAG NAME:
A 10 character user assigned name for each DO can be placed in this datapoint.
MODULAR CONTROLLER QUICK START
3-32