G13
AUTO/MANUAL SWITCH - 1
INPUTS NAME SYMBOL DATAPOINT
CONTROL OUTPUT CO1 C159
AUTO ENABLE AE1 L138
OUTPUT TRACK VALVE OTV1 C165
OUTPUT TRACK SWITCH SWOTV1 L141
PARAMETERS OUTPUT TRACK ENABLE OTE1 L143
HARD MANUAL LIMIT HML1 L146
OUTPUT HIGH LIMIT OH1 C145
OUTPUT LOW LIMIT OL1 C146
OUTPUT SLEW RATE T31 C154
OUTPUTS
OUTPUT OUT1 C138
OUTPUT TRACK STATUS OVTS1 L129
AUTO STATUS AUT1 L131
Description:
The AUTO/MAN Switch selects one of three signals to load into OUT. The signal
selected is either the Output Tracking Value (OTV), the Auto Value (CO) or the
Manual Pushbutton Value. If the Output Tracking Switch (SWOUT) is zero (0) then
OUT = OTV when Output Tracking is enabled (OTE = 1). When the previous
condition is not in effect OUT will equal CO if Auto Enable = 1 and the A/M
pushbutton has set the Auto Switch to 1. When neither previous condition is in effect
the selected signal comes directly from the output increase and decrease pushbut-
tons.